Product Specification
37217
Genset Control for Auto
Start and Transfer Switch
Operation (Model "320/350")
APPLICATIONS
The easYTMgen-320 offers automatic engine starting,
stopping, metering, and generator protection (the
easYTMgen-350 adds AMF, and transfer switching). The
easYTMgen-300 series is designed for isolated opera-
tion.
The multi purpose 6digit 7segment LED offers the ability
to display measured values and alarm messages. The
CAN bus option adds the ability to display messages
from an engine ECU.
O/C
G
Load
O/C
O/C
G
Load
320 & 350
breaker applications
Isolated J1939 CAN bus permits long distance networks
for selected ECU manufacturers. Our sales department
can provide information regarding the selected ECU
manufacturers.
DESCRIPTION
I/O's
• 1 or 3 phase generator and mains true rms
voltage, measuring inputs: rated 480 Vac
(max. 600 Vac)
• Maximum 2 configurable discrete inputs
• Maximum 2 programmable relays
• D+ input (charge alternator input/output)
Protection
(ANSI #)
Generator / Engine: Battery voltage, over-
speed (12), over-/undervoltage (59/27), over-
/underfrequency (81O/U), charge alternator
failure
Features
• Start/stop sequence for Diesel engines
• Pre-glow control
• Operating hours, service hours, and start
counters
• Configurable trip levels/delays/alarm classes
• 6digit 7segment LED for
o display of measuring values (V, f, speed)
o display of counters (see above)
o display of alarms
o display of ECU messages
• PC and/or front panel configurable (selection
of parameters for front panel configuration)
• 15 entry event logger
• Customized display using paper-strips
Differentiation
• Model "320": GCB operation only
• Model "350": GCB and MCB operation
• Generator voltage measurement
o 1phase-2wire
o Option "X": 3phase-4wire, 3phase-3wire,
1phase-3wire, and 1phase-2wire
• Mains voltage measurement
o Model "350": 3phase-4wire
o Model "350X": 3phase-4wire, 3phase-3wire,
1phase-3wire, and 1phase-