This paper provides the calculating of peak time on various possible hours during operating time. According to the surveys and measurement, the peak time will occur at March due to the facing of glass and April due to the wall and roof . In addition, the value of solar heat gain factor SHGF in March for this building is greater than the April on the direction of East, South and West and the SHGF for April is greater than the March on North based on the latitude of Yangon 16.7875N . According to the theoretical analysis, the peak load occurs at 16hour 4PM in March with the amount of 40.459 KW for 4th floor of building envelope. Aung Ko Ko Lwin | Dr. Soe Soe Nu "Calculation for Design Peak Time of Commercial Building using Theoretical Analysis in Tropical Climate Country" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-5 | Issue-1 , December 2020, URL: https://www.ijtsrd.com/papers/ijtsrd35826.pdf Paper URL : https://www.ijtsrd.com/engineering/mechanical-engineering/35826/calculation-for-design-peak-time-of-commercial-building-using-theoretical-analysis-in-tropical-climate-country/aung-ko-ko-lwin
International Journal of Trend in Scientific Research and Development (IJTSRD)
Volume 5 Issue 1, November-December 2020 Available Online: www.ijtsrd.com e-ISSN: 2456 – 6470
@ IJTSRD | Unique Paper ID – IJTSRD35826 | Volume – 5 | Issue – 1 | November-December 2020
Page 74
Calculation for Design Peak Time of Commercial Building
using Theoretical Analysis in Tropical Climate Country
Aung Ko Ko Lwin, Dr. Soe Soe Nu
Master Candidate, Department of Mechanical Engineering,
Yangon Technological University, Yangon, Myanmar
ABSTRACT
This paper provides the calculating of peak time on various possible hours
during operating time. According to the surveys and measurement, the peak
time will occur at March (due to the facing of glass) and April (due to the wall
and roof). In addition, the value of solar heat gain factor (SHGF) in March for
this building is greater than the April on the direction of East, South and West
and the SHGF for April is greater than the March on North based on the
latitude of Yangon (16.7875N). According to the theoretical analysis, the peak
load occurs at 16hour (4PM) in March with the amount of 40.459 KW for 4th
floor of building envelope.
KEYWORDS: air-conditioning, design month peak time, cooling load, peak load
How to cite this paper: Aung Ko Ko Lwin
| Dr. Soe Soe Nu "Calculation for Design
Peak Time of Commercial Building using
Theoretical Analysis in Tropical Climate
Country" Published
in
International
Journal of Trend in
Scientific Research
and
Development
(ijtsrd), ISSN: 2456-
6470, Volume-5 |
Issue-1, December
2020,
pp.74-76,
URL:
www.ijtsrd.com/papers/ijtsrd35826.pdf
Copyright © 2020 by author(s) and
International Journal of Trend in Scientific
Research and Development Journal. This
is an Open Access article distributed
under the terms of
the
Creative
Commons Attribution
License
(CC
BY
4.0)
(http://creativecommons.org/licenses/by/4.0)
I.
INTRODUCTION
Air cond